Horing Lih Q06 Conventional Photoelectric Heat Detector

Conventional Heat Detector

Fire Alarm (FA) System

Characteristics

  • The standard detector is 2-wire or 3-wire. For 4-wire type just add one relay output module on 3-wire base. Simple and easy module placement enables wider application and flexible stock control.
  • Detector is made of high endurance, solid and colorfast Fire-proof plastic.
  • Non-loosening screws on base terminal for easy installation.
  • Detector has passed strict EMC test, which greatly eliminates false alarms caused by interference from nearby sources.
  • Dual LEDs for 360-degree visibility. Bi-color LED, Stand-by Status: Green; Alarm Status: Red.

Specifications
ModelQ06-2Q06-3Q06-4
Alarm ContactN/AN/A0.8A @30V DC
0.4A @125V AC
Voltage Range12 ~ 30V DC
Alarm Current
@24V DC 470Ω
40mA40mA45mA
Standby Current
@24V DC 470Ω
Under 95μA
Thermal Setting58oC
Ambient Temperature-10oC ~ +55oC
MaterialFire-proof plastic
Dimensions (mm)
Dia. x H
102 x 46
Weight115g115g130g
ColorWhite